1、中國南方電網(wǎng)有限責(zé)任公司電網(wǎng)建設(shè)施工作業(yè)指導(dǎo)書 第 8 部分:配網(wǎng)工程198第 8 部分:配網(wǎng)工程臺(tái)架式電力變壓器安裝作業(yè)指導(dǎo)書編碼:DLBYQ04DLBYQ-04 臺(tái)架式電力變壓器安裝作業(yè)指導(dǎo)書目次1 適用范圍 ································&
2、#183;·················································&
3、#183;·················································&
4、#183;················· 22 編寫依據(jù) ······························
5、3;·················································
6、3;·················································
7、3;··················· 23 作業(yè)流程圖 ·····························
8、··················································
9、··················································
10、················· 24 安全風(fēng)險(xiǎn)辨析與預(yù)控 ······························
11、3;·················································
12、3;················································· 25
13、作業(yè)準(zhǔn)備 ·················································&
14、#183;·················································&
15、#183;·················································&
16、#183;·· 56 作業(yè)方法 ·············································
17、3;·················································
18、3;·················································
19、3;········ 67 質(zhì)量控制措施及檢驗(yàn)標(biāo)準(zhǔn) ·······································
20、··················································
21、····································· 811 適用范圍1.1 電壓等級(jí)35kV 及以下配網(wǎng)工程。1.2 電氣類別臺(tái)架變壓器的安裝。2 編寫依據(jù)表 2 編寫依據(jù)序號(hào)引用資料名稱1GBJ 1481
22、990電氣裝置安裝工程電力變壓器、油浸電抗器、互感器施工及驗(yàn)收規(guī)范2GB 501731992電氣裝置安裝工程 35kV 及以下架空電力線路施工及驗(yàn)收規(guī)范3DL/T 5161.32002電氣裝置安裝工程 質(zhì)量檢驗(yàn)及評(píng)定規(guī)程 第 3 部分:電力變壓器、油浸電抗器、 互感器施工質(zhì)量檢驗(yàn);DL/T 5161。102002電氣裝置安裝工程 質(zhì)量檢驗(yàn)及評(píng)定規(guī)程 第 10 部分:35kV 及以下架空電力線路施工質(zhì)量檢驗(yàn)4Q/CSG 111052008南方電網(wǎng)工程施工工藝控制規(guī)范5中國南方電網(wǎng)有限責(zé)任公司基建工程質(zhì)量控制作業(yè)標(biāo)準(zhǔn)(WHS)3 作業(yè)流程圖4安全風(fēng)險(xiǎn)辨析與預(yù)控圖 3 作業(yè)流程圖4.1 臺(tái)架式電力變
23、壓器安裝作業(yè)前,施工項(xiàng)目部根據(jù)該項(xiàng)目作業(yè)任務(wù)、施工條件,參照電網(wǎng)建設(shè)施工安全基準(zhǔn)風(fēng)險(xiǎn)指南(下簡(jiǎn)稱指南)開展針對(duì)性安全風(fēng)險(xiǎn)評(píng)估工作,形成該任務(wù)的風(fēng)險(xiǎn)分析表。4.2 按指南中與臺(tái)架式電力變壓器安裝作業(yè)相關(guān)聯(lián)的電網(wǎng)建設(shè)安全施工作業(yè)票(編碼: DLBYQ0401/01),結(jié)合現(xiàn)場(chǎng)實(shí)際情況進(jìn)行差異化分析,確定風(fēng)險(xiǎn)等級(jí),現(xiàn)場(chǎng)技術(shù)員填寫安全施工作業(yè)票, 安全員審核,施工負(fù)責(zé)人簽發(fā)。4。3 施工負(fù)責(zé)人核對(duì)風(fēng)險(xiǎn)控制措施,并在日站班會(huì)上對(duì)全體作業(yè)人員進(jìn)行安全交底,接受交底的作業(yè)人員負(fù)責(zé)將安全措施落實(shí)到各作業(yè)任務(wù)和步驟中。4。4 安全施工作業(yè)票由施工負(fù)責(zé)人現(xiàn)場(chǎng)持有,工作內(nèi)容、地點(diǎn)不變時(shí)可連續(xù)使用 10 天,超過 1
24、0 天須 重新辦理作業(yè)票,在工作完成后上交項(xiàng)目部保存?zhèn)洳椤1?4。1 作 業(yè)任 務(wù) 安 全 基準(zhǔn)風(fēng) 險(xiǎn) 指南 序號(hào)危 害 名 稱風(fēng)險(xiǎn)種類風(fēng)險(xiǎn)等級(jí)風(fēng)險(xiǎn)控制措施1不按規(guī)定使用或選用不合格登高工具墜落特高的風(fēng)險(xiǎn)按規(guī)定使用安全、合格的登高用具2高空作業(yè)不按規(guī)定佩戴安 全帶墜落特高的風(fēng)險(xiǎn)使用雙保險(xiǎn)安全帶3不用繩索傳遞工具、物料 及不使用工具袋打擊中等風(fēng)險(xiǎn)用繩索傳遞工器具、材料,現(xiàn)場(chǎng)人員必須戴安全帽4混凝土桿施工安全圍蔽措 施不足夾傷 碰撞 打擊中等風(fēng)險(xiǎn)施工現(xiàn)場(chǎng)應(yīng)做好安全圍蔽措施,防止外人進(jìn)入工作 區(qū)域5在道路邊混凝土桿施工沒 有安全圍蔽措施、人員沒穿 反光衣交通意外中等風(fēng)險(xiǎn)在道路旁邊組裝鋼管桿、鐵塔時(shí),
25、施工人員要穿戴 反光衣,按規(guī)定設(shè)置防圍措施和警示標(biāo)志,派專人監(jiān) 護(hù)或協(xié)助疏導(dǎo)交通6起重設(shè)備安全裝置失效墜落 夾傷 打擊高風(fēng)險(xiǎn)起重設(shè)備應(yīng)持有效檢驗(yàn)合格證,安全裝置應(yīng)齊全有效7吊裝沒有設(shè)專人指揮打擊 設(shè)備破損中等風(fēng)險(xiǎn)施工作業(yè)現(xiàn)場(chǎng)協(xié)調(diào)并設(shè)專人統(tǒng)一指揮8起重回轉(zhuǎn)半徑內(nèi)站人打擊 設(shè)備破損中等風(fēng)險(xiǎn)起重機(jī)應(yīng)按吊裝工作半徑就位,回轉(zhuǎn)半徑內(nèi)嚴(yán)禁站人9起重設(shè)備支腿不穩(wěn)打擊 設(shè)備破損高風(fēng)險(xiǎn)各支腿承點(diǎn)必須牢固可靠,在各支腿下應(yīng)加枕木,土質(zhì)松軟的地方應(yīng)加墊鋼板10鋼絲繩套的安全系數(shù)選取不當(dāng)打擊中等風(fēng)險(xiǎn)按吊裝重量選取安全系數(shù)匹配的鋼絲繩套11吊裝 18m 以上電桿時(shí),沒采取補(bǔ)強(qiáng)措施夾傷碰撞中等風(fēng)險(xiǎn)吊裝 18m 以上電桿時(shí)
26、,必須使用補(bǔ)強(qiáng)鋼絲繩12起吊混凝土桿沒有設(shè)調(diào)整繩夾傷 打擊 設(shè)備破損中等風(fēng)險(xiǎn)起吊混凝土桿時(shí)應(yīng)設(shè) 2 根或以上調(diào)整繩13混凝土桿吊點(diǎn)選擇不適當(dāng)夾傷 打擊 設(shè)備破損中等風(fēng)險(xiǎn)鋼管桿、鐵塔起吊點(diǎn)選擇適當(dāng),鋼絲繩綁扎點(diǎn)加軟墊保護(hù)14錨固點(diǎn)布置不合理碰撞 打擊 墜落特高的風(fēng)險(xiǎn)抱桿、電桿、錨固點(diǎn)應(yīng)設(shè)在同一直線上;嚴(yán)格按照設(shè)計(jì)圖紙施工,有專項(xiàng)的施工方案15抱桿與錨固點(diǎn)距離選取不當(dāng),抱桿高度不當(dāng)墜落 打擊 碰撞特高的風(fēng)險(xiǎn)抱桿與錨固點(diǎn)距離應(yīng)符合要求,臨錨、樁錨必須牢固可靠9序號(hào)危 害 名 稱風(fēng)險(xiǎn)種類風(fēng)險(xiǎn)等級(jí)風(fēng)險(xiǎn)控制措施16鄰近帶電設(shè)備變壓器安裝 不滿足安全距離觸電特高的風(fēng)險(xiǎn)必須停電安裝或按帶電操作程序安裝17起吊
27、變壓器沒有設(shè)調(diào)整繩夾傷 打擊 設(shè)備破損中等風(fēng)險(xiǎn)起吊變壓器時(shí)應(yīng)設(shè) 2 根或以上調(diào)整繩18吊裝沒有設(shè)專人指揮打擊 設(shè)備破損中等風(fēng)險(xiǎn)施工作業(yè)現(xiàn)場(chǎng)協(xié)調(diào)并設(shè)專人統(tǒng)一指揮19臨近帶電設(shè)備吊裝作業(yè),起重設(shè)備沒有接地裝置觸電特高的風(fēng)險(xiǎn)確保起重設(shè)備的接地裝置齊全、有效20變壓器未采取有效防傾倒措施設(shè)備破損 打擊 設(shè)備報(bào)廢低風(fēng)險(xiǎn)變壓器底部用枕木墊起,變壓器在臺(tái)架固定牢靠后,才能松開變壓器頂?shù)牡蹉^序號(hào)危 害 名 稱風(fēng)險(xiǎn)種類風(fēng)險(xiǎn)等級(jí)風(fēng)險(xiǎn)控制措施21鄰近帶電設(shè)備吊裝變壓器觸電特高的風(fēng)險(xiǎn)1. 必須滿足施工安全距離;2。 按吊裝規(guī)范進(jìn)行施工22變壓器電機(jī)安裝接線相序錯(cuò)誤設(shè)備燒損高風(fēng)險(xiǎn)做好接線安裝質(zhì)量驗(yàn)收工作23變壓器線纜連
28、接螺栓扭矩不合格設(shè)備燒損中等風(fēng)險(xiǎn)變壓器線纜連接螺栓扭矩必須符合標(biāo)準(zhǔn)要求24變壓器中性線接地?zé)o效設(shè)備破損高風(fēng)險(xiǎn)變壓器中性線需可靠接地,連接扭矩符合要求25變壓器外殼接地?zé)o效觸電中等風(fēng)險(xiǎn)變壓器外殼需可靠接地26變壓器運(yùn)行前沒有打開釋放閥壓片設(shè)備破損中等風(fēng)險(xiǎn)變壓器運(yùn)行前必須打開釋放閥壓片27電焊作業(yè)沒有使用個(gè)人安 全防護(hù)用具灼(燙)傷 觸電高風(fēng)險(xiǎn)1。 嚴(yán)格執(zhí)行電焊作業(yè)規(guī)程;2。 嚴(yán)格執(zhí)行持證上崗制度;3. 潮濕地方應(yīng)使用絕緣墊;4。 正確使用個(gè)人安全防護(hù)用具;5. 電焊機(jī)外殼必須按規(guī)定接地28氣焊作業(yè)沒有使用個(gè)人安 全防護(hù)用具灼(燙)傷中等風(fēng)險(xiǎn)1。 嚴(yán)格執(zhí)行氣焊作業(yè)規(guī)程;2. 嚴(yán)格執(zhí)行持證上崗制度;
29、3. 正確使用個(gè)人安全防護(hù)用具29氣焊用具使用不規(guī)范爆炸中等風(fēng)險(xiǎn)1。 嚴(yán)格執(zhí)行氣焊作業(yè)規(guī)程;2. 嚴(yán)格執(zhí)行持證上崗制度30施工用電不規(guī)范觸電高風(fēng)險(xiǎn)1。 加強(qiáng)使用前及使用過程中的檢查,保護(hù)零線與工 作零線不得混接,開關(guān)箱漏電保護(hù)器靈敏可靠,漏電 保護(hù)裝置參數(shù)應(yīng)匹配;2. 用電管理和檢修維護(hù)必須規(guī)范,并由專業(yè)電工進(jìn)行,配電箱必須上鎖,并采取防雨措施;3。 工作間斷時(shí)切斷電源;4. 必須使用符合要求的線纜,并做好防破損措施31施工區(qū)域防暑降溫措施不 足中暑低風(fēng)險(xiǎn)1. 避開炎熱時(shí)間段作業(yè);2。 配置太陽傘,配置排風(fēng)扇,人員輪流休息;3。 及時(shí)補(bǔ)充水分32不按要求使用梯子墜落中等風(fēng)險(xiǎn)1. 使用合格梯子;
30、2. 設(shè)專人扶梯;3。 擺放位置正確序號(hào)危 害 名 稱風(fēng)險(xiǎn)種類風(fēng)險(xiǎn)等級(jí)風(fēng)險(xiǎn)控制措施33沒有拉閘切斷電源,更換刃具觸電割傷中等風(fēng)險(xiǎn)更換刃具,必須拉閘切斷電源34不按規(guī)范使用轉(zhuǎn)動(dòng)工具絞傷中等風(fēng)險(xiǎn)按操作規(guī)范使用轉(zhuǎn)動(dòng)工具,合理使用個(gè)人安全防護(hù)用品使用轉(zhuǎn)動(dòng)工具時(shí)嚴(yán)禁戴手套5作業(yè)準(zhǔn)備5。 1作業(yè)前施工條件表 5。1作業(yè) 前 施工 條件 序號(hào)項(xiàng)目?jī)?nèi) 容確認(rèn)人說明1任務(wù)單根據(jù)本單位實(shí)際設(shè)置內(nèi)容(包含本項(xiàng)工作)本工序施工負(fù)責(zé)人經(jīng)審批2圖紙?jiān)O(shè)備變更單、設(shè)計(jì)圖紙本工序施工負(fù)責(zé)人經(jīng)審批3預(yù)算材料表含主、輔材本工序施工負(fù)責(zé)人經(jīng)審批4施工方案施工措施、安全技術(shù)交底(項(xiàng)目部級(jí))本工序施工負(fù)責(zé)人經(jīng)審批5相關(guān)證照根據(jù)需要辦理涉
31、及進(jìn)入工作場(chǎng)所的手續(xù)、證件本工序施工負(fù)責(zé)人有效6確認(rèn)上一道工序檢查合格(1)接地電阻不宜大于 4 .(2)確認(rèn)避雷器的各項(xiàng)(絕緣電阻、1mA 時(shí)電壓降、751mA 電壓下的泄漏電流等)試驗(yàn)合格.(3)桿上變壓器可視具體情況在安裝前或安裝后做交接 試驗(yàn),試驗(yàn)結(jié)果必須符合電氣設(shè)備交接試驗(yàn)標(biāo)準(zhǔn)要求,如 在地面試驗(yàn)后再安裝就位,安裝時(shí)應(yīng)采取措施保護(hù)設(shè)備免受撞擊破損,尤其應(yīng)注意防止電瓷部件的損壞。如先試驗(yàn)后安裝的情況,在本節(jié)作業(yè)流程圖中沒有下接試驗(yàn)工序,交接試驗(yàn)就是上一道工序本工序施工負(fù)責(zé)人合格5。 2人員、主要工器具及儀器儀表配置表 5。2 人員、主要工器具及儀器儀表配置序號(hào)項(xiàng)目?jī)?nèi) 容說 明1人員配置
32、施工階段建議工作人數(shù)現(xiàn)場(chǎng)施工負(fù)責(zé)人現(xiàn)場(chǎng)施工 質(zhì)安員技術(shù)崗位必須持有與作業(yè)工種 相應(yīng)、有效的上崗證,輔助工不 得從事電氣設(shè)備安裝等專業(yè)工作臺(tái)架安裝技術(shù)工人 5+輔助工 211變壓器本體安裝技術(shù)工人 5+輔助工 2配套設(shè)備 安裝技術(shù)工人 3一次接線技術(shù)工人 3附件安裝技術(shù)工人 32施工內(nèi)容相 對(duì)應(yīng)的設(shè)備 材料油浸變壓器、避雷器、高壓跌落式熔斷器、混凝土電桿、 導(dǎo)線、3.5m 角鐵橫擔(dān)、槽鋼、8 號(hào)鐵線、防蛙罩、絕緣護(hù)套、 螺釘、金具、瓷擔(dān)、枕木等(1)核對(duì)材料、設(shè)備及附件的到位及數(shù)量。(2)核對(duì)變壓器技術(shù)參數(shù),各項(xiàng) 參數(shù)符合設(shè)計(jì)要求。檢查變壓器的 外觀應(yīng)無銹蝕及機(jī)械損傷,儲(chǔ)油柜油位正常,油箱無滲漏
33、現(xiàn)象、無受潮,瓷套光滑無裂紋、缺損。(3)混凝土電桿及構(gòu)件必須符 合國家標(biāo)準(zhǔn)。檢查電桿表面光滑 平整,鋼筋無偏心現(xiàn)象,內(nèi)外壁 厚度均勻,無露筋、跑漿現(xiàn)象。無縱向裂縫,橫向裂紋不 超過0。1mm,長度不超過 1/3 周長。預(yù) 應(yīng)力桿不能有縱、橫向裂縫。桿 身彎曲不超過桿長 1/1000;鋼圈 連接的混凝土電桿,鋼板圈焊口 處內(nèi)壁的混凝土端面與焊口處距離不得小于 10mm。(4)核對(duì)避雷器的技術(shù)性能、 參數(shù)符合設(shè)計(jì)要求。檢查避雷器 的瓷件(復(fù)合外套)無裂紋、破 損,瓷鐵黏合牢固。(5)核對(duì)高壓跌落式熔斷器的 技術(shù)性能、參數(shù)和安裝的熔絲符 合設(shè)計(jì)要求。檢查高壓跌落式熔 斷器的各部分零件完整;轉(zhuǎn)軸光
34、滑靈活,鑄件不應(yīng)有裂紋、砂眼、 銹蝕;瓷件良好,熔絲管不應(yīng)有 吸潮膨脹或彎曲現(xiàn)象.(6)收集所有設(shè)備出廠合格證明文件及技術(shù)資料3施工內(nèi)容相 對(duì)應(yīng)的器 具、機(jī)械及 工器具儀表工器具:焊接工具、水平儀、鋼鍬、鋼管、千斤頂、壓接鉗、手錘、大錘、鐵鏟、扳手、梯子、尺子、繩索等。機(jī)械:根據(jù)變壓器型號(hào)、規(guī)格,準(zhǔn)備車輛、起重機(jī)具或叉 車及吊裝機(jī)具等(1)根據(jù)現(xiàn)場(chǎng)情況使用的工器具、機(jī)械符合相關(guān)要求。(2)鋼絲繩荷重,須保證其安 全系數(shù),根據(jù)起重機(jī)具臂角度確 定荷載,不得超載使用4完成開工 程序工作負(fù)責(zé)人向項(xiàng)目負(fù)責(zé)人報(bào)開工,并由項(xiàng)目負(fù)責(zé)人完成向監(jiān)理單位開工報(bào)審手續(xù)施工準(zhǔn)備完成可報(bào)開工,當(dāng)施 工準(zhǔn)備不足時(shí),上報(bào)該
35、項(xiàng)目負(fù)責(zé)人協(xié)調(diào)解決6作業(yè)方法表 6作業(yè)方法序號(hào)項(xiàng)目?jī)?nèi) 容說 明1作業(yè) 前工 作(1)現(xiàn)場(chǎng)施工負(fù)責(zé)人向進(jìn)入本施工范圍的所有工作人員明確交待本次 施工設(shè)備狀態(tài)、作業(yè)內(nèi)容、作業(yè)范圍、進(jìn)度要求、特殊項(xiàng)目施工要求、 作業(yè)標(biāo)準(zhǔn)、安全注意事項(xiàng)、危險(xiǎn)點(diǎn)及控制措施、危害環(huán)境的相應(yīng)預(yù)防控制措施、人員分工,并簽署(班組級(jí))安全技術(shù)交底表。(2)工作負(fù)責(zé)人負(fù)責(zé)辦理相關(guān)的工作許可手續(xù),開工前做好現(xiàn)場(chǎng)施工防護(hù)圍蔽警示措施,夜間施工的,須有足夠的照明。(3)現(xiàn)場(chǎng)施工負(fù)責(zé)人組織檢查確認(rèn)進(jìn)入本施工范圍的所有工作人員正 確使用勞保用品和著裝,并帶領(lǐng)施工作業(yè)人員進(jìn)入作業(yè)現(xiàn)場(chǎng)按安規(guī)規(guī)定佩戴統(tǒng)一的安全 帽,統(tǒng)一佩戴有個(gè)人照片的作 業(yè)證
36、(或胸卡證),穿著統(tǒng)一的 工作服2開始 主要 作業(yè)現(xiàn)場(chǎng)施工負(fù)責(zé)人發(fā)出許可開工命令3臺(tái)架(1)電桿的組立按照本冊(cè)架空線路施工桿塔工程相關(guān)部分的要求進(jìn)行現(xiàn)場(chǎng)施工負(fù)責(zé)人正確、安全銅線鋁線引上線16mm225mm2引下線25mm235mm2安裝作業(yè) 程序施工。(2)鋼圈連接的混凝土電桿焊接應(yīng)符合規(guī)范要求,電桿組立后金屬部分涂防銹漆做防腐蝕處理.(3)雙桿式配電變壓器臺(tái)架宜采用槽鋼,槽鋼厚度應(yīng)大于 10mm,并經(jīng)熱鍍鋅處理,其強(qiáng)度應(yīng)滿足載重變壓器的要求。(4)臺(tái)架離地面不應(yīng)少于 2.5m;安置配電變壓器的槽鋼臺(tái)架應(yīng)保持水平,雙桿式配電變壓器臺(tái)架水平傾斜不大于臺(tái)架根開的 1/100。(5)容量為 315k
37、VA 及其以上的變壓器槽鋼臺(tái)架,應(yīng)加裝槽鋼撐臂或頂樁支撐地組織作業(yè),現(xiàn)場(chǎng)施工質(zhì)安員負(fù)責(zé)現(xiàn)場(chǎng)作業(yè)全過程的安全、 質(zhì)量監(jiān)控4本體 安裝 作業(yè) 程序(1)桿上變壓器的臺(tái)架緊固檢查后,才能吊裝變壓器且就位固定。(2)變壓器在裝卸、就位的過程中,設(shè)專人負(fù)責(zé)統(tǒng)一指揮,指揮人員發(fā)出的指揮信號(hào)必須清晰、準(zhǔn)確.(3)采用起重機(jī)具裝卸、就位時(shí),起重機(jī)具的支撐腿必須穩(wěn)固,受力 均勻。應(yīng)準(zhǔn)確使用變壓器油箱頂蓋的吊環(huán),吊鉤應(yīng)對(duì)準(zhǔn)變壓器重心,吊 掛鋼絲繩間的夾角不得大于 60°。起吊時(shí)必須試吊,防止鋼索碰損變壓 器瓷套管。起吊過程中,在吊臂及吊物下方嚴(yán)禁任何人員通過或逗留, 吊起的設(shè)備不得在空中長時(shí)間停留。(4
38、)變壓器就位移動(dòng)時(shí),應(yīng)緩慢移動(dòng),不得發(fā)生碰撞及不應(yīng)有嚴(yán)重的沖擊和震蕩,以免損壞絕緣構(gòu)件。(5)變壓器底部用枕木墊起,變壓器在臺(tái)架固定牢靠后,才能松開變壓器頂?shù)牡蹉^。(6)變壓器安裝后,套管表面應(yīng)光潔,不應(yīng)有裂紋、破損等現(xiàn)象;套管壓線螺栓等部件應(yīng)齊全,且安裝牢固;儲(chǔ)油柜油位正常,外殼干凈現(xiàn)場(chǎng)施工負(fù)責(zé)人正確、安全 地組織作業(yè),現(xiàn)場(chǎng)施工質(zhì)安員 負(fù)責(zé)現(xiàn)場(chǎng)作業(yè)全過程的安全、 質(zhì)量監(jiān)控5配套 設(shè)備 安裝 作業(yè) 程序高壓跌落式熔斷器、避雷器等高壓設(shè)備按照本冊(cè)戶內(nèi)外電氣設(shè)備施工戶外電氣設(shè)備安裝工程相關(guān)部分的要求進(jìn)行施工現(xiàn)場(chǎng)施工負(fù)責(zé)人正確、安全地 組織作業(yè),現(xiàn)場(chǎng)施工質(zhì)安員負(fù)責(zé) 現(xiàn)場(chǎng)作業(yè)全過程的安全、質(zhì)量監(jiān) 控6
39、一次 接線 作業(yè) 程序(1)導(dǎo)線在施工前應(yīng)先用尺子實(shí)際測(cè)量各跨安裝點(diǎn)的準(zhǔn)確長度,根據(jù) 施工需要進(jìn)行切割。(2)導(dǎo)線壓接后不應(yīng)使管口附近導(dǎo)線有隆起和松股,管表面應(yīng)光滑,無裂紋。金具壓接后,均應(yīng)倒棱,去毛刺。(3)導(dǎo)線連接可靠,搭接面清潔、平整、無氧化層,涂有電力復(fù)合脂,符合規(guī)范要求。(4)兩端遇有銅鋁連接時(shí),應(yīng)設(shè)有過渡措施。(5)銅接線端子搭接面必須進(jìn)行搪錫處理.(6)高壓跌落式熔斷器、避雷器的引線應(yīng)安裝牢固、排列整齊美觀。引線相間距離及對(duì)地距離應(yīng)符合規(guī)定要求。(7)高壓跌落式熔斷器上引線與銅三角符的連接應(yīng)采用帶電夾頭.(8)避雷器引線的連接不應(yīng)使端子受到超過準(zhǔn)許的外加應(yīng)力。(9)高壓避雷器的引
40、線其截面應(yīng)滿足以下要求.(10)變壓器外殼、臺(tái)架應(yīng)可靠接地;避雷器接地引下線、低壓側(cè)中 性點(diǎn)均應(yīng)與兩條電桿的接地引線分別可靠連接(兩點(diǎn)接地),接地線與 主接地網(wǎng)的連接應(yīng)滿足設(shè)計(jì)及規(guī)范要求。(11)雙電纜出線接線端子必須分別在設(shè)備接線端子兩側(cè)搭接。(12)裸露帶電部分宜進(jìn)行絕緣處理。(13)戶外一次接線應(yīng)采用熱鍍鋅螺栓連接,所用螺栓應(yīng)有平墊圈和彈簧墊片,螺栓緊固后,螺栓宜露出 23 絲扣。(14)導(dǎo)線應(yīng)相色標(biāo)識(shí)正確清晰現(xiàn)場(chǎng)施工負(fù)責(zé)人正確、安全 地組織作業(yè),現(xiàn)場(chǎng)施工質(zhì)安員 負(fù)責(zé)現(xiàn)場(chǎng)作業(yè)全過程的安全、 質(zhì)量監(jiān)控。(1)接地體的焊接面圓鋼為 單雙面焊接、扁鋼為四面焊接, 焊口可靠、滿焊;采用搭接時(shí),
41、搭接長度:圓鋼雙面焊接為直 徑的 6 倍、圓鋼單面焊接為直 徑的 12 倍,扁鋼為寬度的 2 倍。(2)接地體焊接完畢冷卻后, 應(yīng)涂上防腐油漆7附件 安裝 作業(yè) 程序(1)吸濕器安裝時(shí)取下隔離片,吸濕器必須與儲(chǔ)油柜連通,硅膠干燥、 不受潮。全密封(不帶儲(chǔ)油柜)變壓器運(yùn)行前必須打開釋放閥壓片。(2)變壓器臺(tái)架懸掛標(biāo)志、警告牌等參照設(shè)計(jì)圖紙上級(jí)單位驗(yàn)收相關(guān)標(biāo)準(zhǔn)及文件的要求設(shè)置現(xiàn)場(chǎng)施工負(fù)責(zé)人正確、安全 地組織作業(yè),現(xiàn)場(chǎng)施工質(zhì)安員 負(fù)責(zé)現(xiàn)場(chǎng)作業(yè)全過程的安全、 質(zhì)量監(jiān)控7質(zhì)量控制措施及檢驗(yàn)標(biāo)準(zhǔn)7.1 質(zhì)量控制措施7。1.1 現(xiàn)場(chǎng)負(fù)責(zé)人應(yīng)根據(jù)現(xiàn)場(chǎng)情況安排技術(shù)人員負(fù)責(zé)質(zhì)量監(jiān)控。7。1.2 作業(yè)人員必須熟悉工
42、程作業(yè)流程和質(zhì)量檢驗(yàn)標(biāo)準(zhǔn);技術(shù)崗位人員必須持有與作業(yè)相應(yīng)、有效的上崗證。7.1.3 現(xiàn)場(chǎng)負(fù)責(zé)人在進(jìn)行安全技術(shù)交底時(shí)必須詳細(xì)介紹本作業(yè)質(zhì)量控制要點(diǎn)、常見的質(zhì)量通病及其防治措施。7。1。4 作業(yè)現(xiàn)場(chǎng)必須有經(jīng)審核批準(zhǔn)的設(shè)計(jì)圖紙和施工方案,作業(yè)人員必須按圖施工。7.1.5 施工質(zhì)量檢驗(yàn)一般按以下方式進(jìn)行。質(zhì)量檢驗(yàn)一般采用三級(jí)檢驗(yàn)制,施工隊(duì)(組)對(duì)所施工的分項(xiàng)工程應(yīng)進(jìn)行 100%的質(zhì)量自檢;項(xiàng)目部對(duì)所負(fù)責(zé)施工的分部工程和單位工程組織質(zhì)量檢查,復(fù)檢比例不宜低于 50%;公司對(duì)單位工程組織檢查,抽檢比例不宜低于 20%。7.1.6 隱蔽工程施工完成以及全部工序作業(yè)完成(轉(zhuǎn)序)時(shí),必須提前 24 小時(shí)通知監(jiān)理現(xiàn)場(chǎng)驗(yàn)收。7。2 質(zhì)量控制點(diǎn)表 7。2 質(zhì)量控制點(diǎn)表單控制點(diǎn)控制方式WHS臺(tái)架式變壓器安裝工程7。3 檢驗(yàn)標(biāo)準(zhǔn)質(zhì)量檢驗(yàn)按10kV500kV 輸變電及配電工程質(zhì)量驗(yàn)收與評(píng)定標(biāo)準(zhǔn)第 8 冊(cè):配網(wǎng)工程中的 Q/CSG 表8-7。6 要求執(zhí)行.附件 1安全施工作業(yè)票編碼:DLBYQ-0401/01工作時(shí)間工作地點(diǎn)技術(shù)員現(xiàn)場(chǎng)安全員現(xiàn)場(chǎng)負(fù)責(zé)人安全風(fēng)險(xiǎn)分析及控制措施序號(hào)危害名稱風(fēng)險(xiǎn)種類風(fēng)險(xiǎn)等級(jí)風(fēng)險(xiǎn)控制措施1不按規(guī)定
溫馨提示
- 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請(qǐng)下載最新的WinRAR軟件解壓。
- 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請(qǐng)聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
- 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁內(nèi)容里面會(huì)有圖紙預(yù)覽,若沒有圖紙預(yù)覽就沒有圖紙。
- 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
- 5. 人人文庫網(wǎng)僅提供信息存儲(chǔ)空間,僅對(duì)用戶上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對(duì)用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對(duì)任何下載內(nèi)容負(fù)責(zé)。
- 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請(qǐng)與我們聯(lián)系,我們立即糾正。
- 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時(shí)也不承擔(dān)用戶因使用這些下載資源對(duì)自己和他人造成任何形式的傷害或損失。
最新文檔
- 2022屆高考英語一輪復(fù)習(xí)閱讀理解專項(xiàng)訓(xùn)練(一)
- 河北省邯鄲市成安縣2024-2025學(xué)年八年級(jí)下學(xué)期期中歷史試題(含答案)
- 《高等數(shù)學(xué)》上冊(cè)課件06-05二階常系數(shù)線性齊次微分方程
- 2025年廣告學(xué)基礎(chǔ)知識(shí)能力測(cè)試試卷及答案
- 百貨公司培訓(xùn)
- 直接包裝機(jī)立項(xiàng)投資項(xiàng)目可行性研究報(bào)告
- 《自媒體營銷》課件項(xiàng)目一自媒體營銷概述
- 多發(fā)肋骨骨折術(shù)后護(hù)理
- 第1章 勾股定理 問題解決策略 課件 北師大版數(shù)學(xué)八年級(jí)上冊(cè)
- 內(nèi)科危重患者健康教育
- 數(shù)字美的智慧工業(yè)白皮書-2023.09
- 橋梁施工進(jìn)度圖
- 某啤酒廠安全現(xiàn)狀評(píng)價(jià)設(shè)計(jì)報(bào)告書模板
- 在線語言學(xué)習(xí)行業(yè)競(jìng)爭(zhēng)格局分析
- 廣西桂林市2022-2023學(xué)年高二下學(xué)期期末質(zhì)量檢測(cè)數(shù)學(xué)試題(含答案解析)
- 內(nèi)墻抹灰安全技術(shù)交底
- 中學(xué)美術(shù)校本教材《素描》
- 國開2023年春《理工英語1》機(jī)考網(wǎng)考期末復(fù)習(xí)資料參考答案
- 《幼兒生活活動(dòng)保育》課程標(biāo)準(zhǔn)
- 年出欄5萬頭生豬養(yǎng)殖場(chǎng)建設(shè)項(xiàng)目及年出欄4800頭生豬養(yǎng)殖基地建設(shè)項(xiàng)目建議書
- OIF-CEI-04.0OIF-CEI-04.0高速電口標(biāo)準(zhǔn)
評(píng)論
0/150
提交評(píng)論