1、1. Insulation resistance test絕緣電阻試驗The insulation resistance between bus-bar to earth and the resistance between bus-bars (include 220Vpanel) each phase, shall be measured by a DC 500V megger. Test to be before and after continuous load test.在所有主配電板的開關及保險絲處于斷開位置時,用直流500伏兆歐表測量匯流排對地的絕緣電阻,及匯流排(包括220V屏)

2、各相之間絕緣電阻。2. Reverse power relay trip test逆功率繼電器脫扣試驗Reverse power relay must delay act correctly, the ACB break delay. Reverse power setting: 10% rated power (70kW) Setting time: 10 secondsThe result of test should be recorded into the No.1 tables.逆功率繼電器必須正確延時動作,空氣短路延時斷開。逆功率設定值:10%額定功率(70KW)設定時間:105%

3、(472.5V) delay 10 second alarm, trip, stand-by generator start and switch on. 匯流排電壓高105%(472.5V)以上,延時10秒報警,脫扣,備用機起 動并合閘。 (b)Bus voltage low 95% (427.5V) delay 10 seconds alarm, trip, stand-by generator start and switch on 匯流排電壓低95% (427.5V)以下,延時10秒報警,脫扣,備用機起 動合閘。 (c) Frequency low 105%(63Hz) 10 seco

4、nds alarm,trip, stand-by generator start and switch on 頻率高105%(63Hz)以上,延時10秒報警,脫扣,備用機組起動合閘。 (e)Bus no-voltage (main power failure) stand-by generator start and switch on 匯流排失壓(全船失電)備用起動并合閘 (f) General alarm trip and emergency stop 公共報警 脫扣并緊急停車 (g) Start failure alarm 起動故障 報警(3) When three generators

5、 running at automatic mode, two running in parallel and another set is stand-by. If any of the running generators trip, the stand-by set shall start automatically and running in parallel, the failure generator quit running. 三臺發電機自動模式時,二臺并聯運行,另一臺作備用發電機,當任何一臺運行中的發電機故障脫扣,備用機組自動起動,并聯運行,故障機退出運行。(4) Runni

6、ng in parallel automatically and switchover automatically test. 自動并聯運行和自動切換運行試驗This test is carried out refer to “the process chart of generator control” and verify good programming control and following function control. 可參照“發電機控制流程圖”所示的控制程序進行,并驗證良好的程序控制和下列控制功能。 (a)Generator start automatically 發電機

7、自動起動 (b)Automatic synchronization 自動同步 (c)During the period of parallel running the loads shall be distributed automatically 并聯運行期間的自動負荷分配 (d)During the period of generators changing the loads shall be transfer automatically 發電機轉換期間的自動負荷轉移 (e)When the net power exceed power of single generator 90% v

8、ia automatic load detection, the stand-by generators shall started delay 10 sec and then running. 通過自動負荷檢測,當網上功率超過單機功率的90%時,備用機組延時10秒起動并投入 (f)Two sets of generators run in parallel, when the total loads is under single power 70%, loads shall be shifted to one generator automatically after 5 minute c

9、ontinuously running, the other generator disconnected automatically and shut down delay under no-load condition. 二臺并聯運行時,若總負荷為單機功率的70%以下時,持續5分鐘后負荷自動轉移至一臺發電機,另一臺發電機自動分閘后空載停車(5) MSB safety protection alarm see No.4 tables. 主配電板安全保護報警點見表格4。Test of reverse power(cos=1.0)逆功率試驗(Table1 表1)Generator發電機TestO

10、peration power(kW)動作功率Time(sec)時間Remarks備注NO.1 D/G1st702nd“NO.2 D/G1st“2nd“NO.3 D/G1st“2nd70 Test of over current過電流試驗(Table1 表2)D/GIt1=1122.6(Io) x 1.1 x 120%=1482A It2=270%x1122.6(Io) =3031AE/GIt1=240.6(Io) x 1.1 x 120%=318AIt2=300%x240.6(Io) =722AGeneratorTestOperation current(A)Time (sec)remarks

11、NO.1 D/G1st2ndNO.2 D/G1st2ndNO.3 D/G1st2ndE/G1st2ndTest of over current for pref. trip過電流優先脫扣試驗(Table1 表3)IP=120%x1122.6(Io)=1347AGeneratorTestOperation current(A)Time(sec)RemarksNO.1 D/G1st2ndNO.2 D/G1st2ndNO.3 D/G1st2ndTable 4 (表格4)序號No.項目items報警Alarm0601Main busbar voltage high主匯流排電壓高0602Main bus

12、bar voltage low主匯流排電壓低0603Main busbar frequency high主匯流排頻率高0604Main busbar frequency low主匯流排頻率低06051st preference trip一級優先脫扣06062st preference trip二級優先脫扣0607MSB common alarm主配電板公共故障0608Emcy stop line break應急切斷線路0609Auto synchro failure自動同步故障0610PMS failure電站管理系統故障0613G1 ACB abnormal trip1#發電機斷路器異常脫扣

13、0614G2 ACB abnormal trip2#發電機斷路器異常脫扣0615G3 ACB abnormal trip3#發電機斷路器異常脫扣0616G1 ACB non close1#發電機斷路器未閉合0617G2 ACB non close2#發電機斷路器未閉合0618G3 ACB non close3#發電機斷路器未閉合0619MSB DC 24V source fail主配電板24V電源故障0620MSB 440V low insulation主配電板440V絕緣低0621MSB 220V low insulation主配電板220V絕緣低0623MSB Emcy stop &pref trip control source fail主配電板應急切斷/優先脫扣電源故障G1 ACB re

溫馨提示

  • 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請下載最新的WinRAR軟件解壓。
  • 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請聯系上傳者。文件的所有權益歸上傳用戶所有。
  • 3. 本站RAR壓縮包中若帶圖紙,網頁內容里面會有圖紙預覽,若沒有圖紙預覽就沒有圖紙。
  • 4. 未經權益所有人同意不得將文件中的內容挪作商業或盈利用途。
  • 5. 人人文庫網僅提供信息存儲空間,僅對用戶上傳內容的表現方式做保護處理,對用戶上傳分享的文檔內容本身不做任何修改或編輯,并不能對任何下載內容負責。
  • 6. 下載文件中如有侵權或不適當內容,請與我們聯系,我們立即糾正。
  • 7. 本站不保證下載資源的準確性、安全性和完整性, 同時也不承擔用戶因使用這些下載資源對自己和他人造成任何形式的傷害或損失。

評論

0/150

提交評論